| Bus
ducts up to 8,000 amp rating are totally enclosed
type having robust construction. Bus ducts are
designed to provide ease of inspection & maintenance.
Enclosure type can be designed
to suit indoor or outdoor installation. Space
heaters, silica gel breathers are provided to
minimize moisture content inside the bus duct.
Individual bus sections are properly joined to
minimize voltage drop & avoid heating. Flexible
connections are used at end termination points.
Rubber bellows can also be provided at termination
point against specific requirements.
Expansion joints are used if straight
length of any section exceeds 6 mtr.
Suitable sized earth bus is provided
from out side at the bottom which runs parallel
to the bus duct.
FRP shielding plates are used
in wall crossing units to ensure plant safety.
Bus bars of copper or aluminum are selected to
meet the continuous current rating and desired
short circuit levels in single tier or double
tier dispositions and in both interleaved and
non-interleaved dispositions.
|
|
Application |
Power
Distribution & Transmission |
|
Operational
Current |
8000A |
|
Operational
Voltage |
415
V |
|
Rated
Insulation Voltage |
690
V |
|
Ambient
Temperature |
45
Deg.C |
|
Form
of Separation |
Non
Segregated |
|
Type
Test Performed |
Short
Circuit Withstand, degree of protection
& temperature rise for ducts
upto 5200 A, 415 V & 1600A,
11 kV. |
|
Degree
of Protection |
IP
: 55 |
|
|